Abstract
The paper describe using of developed model for series capacitor protected by metal oxide varistor (MOV) based on the Describing function method (or method of harmonic balance) in short circuit studies. Symmetrical and unsymmetrical faults are concerned using compensation technique and the implementation of the method in classical short circuit analysis. The results are compared with existing empirical model.
Original language | English |
---|---|
Pages | 655-658 |
Number of pages | 4 |
Publication status | Published - 1999 |
Externally published | Yes |
Event | Proceedings of the 1999 5th IEEE AFRICON Conference 'Electrotechnical Services for Africa' - Cape Town, S Afr Duration: 28 Sept 1999 → 1 Oct 1999 |
Conference
Conference | Proceedings of the 1999 5th IEEE AFRICON Conference 'Electrotechnical Services for Africa' |
---|---|
City | Cape Town, S Afr |