Assessment and Optimization of Double Earth Fault Treatment in Distance Protection in Isolated or Compensated Networks

  • Hysni Sali

    Studienabschlussarbeit: Masterarbeit

    Abstract

    Detecting Double Earth Faults poses a significant challenge in Isolated or Compensated networks due to the involvement of high short-circuit currents. However, the protection against Double Earth Fault in distance protection is a difficult task. The research is concentrated on developing highly accurate methods for detecting Double Earth Faults. Three methods are presented to detect the Double Earth Faults in distance protection such as, voltage and current symmetrical components, impedance variations and delta quantities of voltages and currents (comparing fault values with pre-fault levels). The first method depends on the examination of symmetrical components of voltage and current, which encompass positive, negative, and zero sequences. By examining the relation between these sequences during various faults, distinct planes for fault recognition are established. The decision for plane selection is based on three settings: the zero sequence voltage, the zero sequence current and negative sequence current. Following fault recognition, the phase selection decision is made using the angular relation between sequences. The impedance variation method involves observing alterations in phase-to-phase and phase-to-earth impedances between fault and pre-fault conditions, in accordance with the 1.5 × Zmin (minimum impedance) criterion. The impedance variation method can distinguish between single earth faults and Double Earth Faults. In the events of Double Earth Faults, the phase selection is done via estimating the scale of variation in phase-to-earth impedances where two of phase-to-earth impedances with the highest variation are selected as the faulty phases. The Delta quantities of voltages and current provide a measure of imbalances, which appear during a fault event and help assess the severity of faults in the system. In the occasion of Double Earth Faults, the primary objective is typically to deactivate one of the earth faults based on the selected phase preference. The remaining ground fault either selfextinguishes or is manually switched off. The effectiveness of the fault recognition methods is evaluated through simulations for different transmission line lengths (ranging from 30 to 200 km) and voltage levels (ranging from 20 to 400 kV). The influence of fault impedance values on the methods is observed across different fault impedance values, including 2 Ω, 10 Ω, 20 Ω and 50 Ω. In conclusion, the developed methods are very accurate and reliable for fault recognition, demonstrating a reaction speed of 20 milliseconds, even though when the system is overloaded or without load. Methods respond correctly even for different fault impedances insinuating the real-world grids.
    Datum der Bewilligung2024
    OriginalspracheEnglisch
    Betreuer/-inRastko Zivanovic (Betreuer*in)

    Studiengang

    • Electrical Engineering

    Zitieren

    '