Identification of the resonant-grounded system parameters by evaluating fault measurement records

Rastko Živanović, Peter Schegner, Olaf Seifert, Georg Pilz

Publikation: Beitrag in FachzeitschriftArtikelBegutachtung

40 Zitate (Scopus)

Abstract

The operation of a resonant-grounded network during an earth-fault condition depends on the three basic parameters: damping, detuning, and unbalance factor. These parameters are influenced by the environmental conditions (e.g. humidity, temperature, and pollution), and the network topology. Accurate values of these parameters during an earth-fault condition are required to examine the operation of the compensation system. The fault records could be used for that purpose. The recorded neutral-to-ground voltage signals have been parameterized (using damping and detuning as parameters) according to the mathematical model of the transient process. Iteratively reweighted least squares algorithm has been used to fit the model. This algorithm is the major improvement over the classical least squares approach. It is able to filter out noise more efficiently. As a direct result, very accurate parameter identification has been achieved. This paper concludes with the practical examples.

OriginalspracheEnglisch
Seiten (von - bis)1085-1090
Seitenumfang6
FachzeitschriftIEEE Transactions on Power Delivery
Jahrgang19
Ausgabenummer3
DOIs
PublikationsstatusVeröffentlicht - Juli 2004
Extern publiziertJa

Fingerprint

Untersuchen Sie die Forschungsthemen von „Identification of the resonant-grounded system parameters by evaluating fault measurement records“. Zusammen bilden sie einen einzigartigen Fingerprint.

Zitieren