TY - JOUR
T1 - Global sensitivity analysis of transmission line fault-locating algorithms using sparse grid regression
AU - Živanović, Rastko
PY - 2012/11
Y1 - 2012/11
N2 - Computation of distance to fault on an electrical transmission line is affected by many sources of uncertainty, including parameter setting errors, measurement errors, as well as absence of information and incomplete modelling of a system under fault condition. In this paper we propose an application of the variance-based global sensitivity measures for evaluation of fault location algorithms. The main goal of the evaluation is to identify factors and their interactions that contribute to the fault locator output variability. This analysis is based on the results of Sparse Grid Regression. The method compiles the Functional ANOVA model to represent fault locator output as a function of uncertain factors. The ANOVA model provides a tool for interpretation and sensitivity analysis. In practice, such analysis can help in functional performance tests, especially in: selection of the optimal fault location algorithm (device) for a specific application, calibration process and building confidence in a fault location function result. The paper concludes with an application example which demonstrates use of the proposed methodology in testing and comparing some commonly used fault location algorithms. This example is also used to demonstrate numerical efficiency for this type of application of the proposed Sparse Grid Regression method in comparison to the Quasi-Monte Carlo approach.
AB - Computation of distance to fault on an electrical transmission line is affected by many sources of uncertainty, including parameter setting errors, measurement errors, as well as absence of information and incomplete modelling of a system under fault condition. In this paper we propose an application of the variance-based global sensitivity measures for evaluation of fault location algorithms. The main goal of the evaluation is to identify factors and their interactions that contribute to the fault locator output variability. This analysis is based on the results of Sparse Grid Regression. The method compiles the Functional ANOVA model to represent fault locator output as a function of uncertain factors. The ANOVA model provides a tool for interpretation and sensitivity analysis. In practice, such analysis can help in functional performance tests, especially in: selection of the optimal fault location algorithm (device) for a specific application, calibration process and building confidence in a fault location function result. The paper concludes with an application example which demonstrates use of the proposed methodology in testing and comparing some commonly used fault location algorithms. This example is also used to demonstrate numerical efficiency for this type of application of the proposed Sparse Grid Regression method in comparison to the Quasi-Monte Carlo approach.
KW - Global sensitivity analysis
KW - Quasi-Monte Carlo
KW - Sparse grid integration
KW - Sparse grid regression
KW - Transmission lines
UR - http://www.scopus.com/inward/record.url?scp=84866334529&partnerID=8YFLogxK
U2 - 10.1016/j.ress.2011.12.005
DO - 10.1016/j.ress.2011.12.005
M3 - Article
AN - SCOPUS:84866334529
SN - 0951-8320
VL - 107
SP - 132
EP - 138
JO - Reliability Engineering and System Safety
JF - Reliability Engineering and System Safety
ER -